Bussmann LP-CC-20

Bussmann LP-CC-20 Time Delay Fuse 20A Instruction Manual

Model: LP-CC-20

1. המוצר נגמרview

The Bussmann LP-CC-20 is a Low-Peak, current-limiting, time-delay cartridge fuse designed for reliable circuit protection. This 20 Amp fuse is rated for 600 Volts AC or less and 300 Volts DC, making it suitable for a wide range of industrial and commercial applications where protection against both overcurrents and short circuits is critical.

Its time-delay characteristic allows for temporary overcurrents, such as those caused by motor starting, without nuisance tripping, while still providing fast-acting protection for short-circuit conditions.

Bussmann LP-CC-20 Time Delay Fuse

איור 1: Bussmann LP-CC-20 Time Delay Fuse. This image shows the cylindrical body of the fuse with end caps, typical of a cartridge fuse design.

2. מידע בטיחות

אַזהָרָה: Electrical work can be dangerous. Always follow local electrical codes and safety regulations. Improper installation or handling of electrical components can result in serious injury or death.

  • Ensure power is disconnected at the main circuit breaker or switch before installing, removing, or inspecting fuses.
  • השתמשו בציוד מגן אישי (PPE) מתאים, כגון כפפות מבודדות ומשקפי בטיחות.
  • Only replace fuses with those of the exact same type, voltage, and current rating (e.g., LP-CC-20). Using an incorrect fuse can lead to fire, equipment damage, or inadequate protection.
  • אל תעקוף או לאampעם נתיכים.
  • If unsure about any electrical procedure, consult a qualified electrician.

3. מפרטים

תְכוּנָהעֵרֶך
מספר דגםLP-CC-20
מותגבוסמן
סוג נתיךLow-Peak, Current Limiting, Time-Delay Cartridge Fuse
דירוג נוכחי20 Amps
כרך ידtage דירוג600 Volts AC (or less), 300 Volts DC
מידות (L x W x H)2.00 x 1.00 x 1.00 אינץ' בערך
מִשׁקָלבערך 0.33 פאונד
הַתאָמָהתואם RoHS
UPC653829011452

4. התקנה והגדרה

This fuse is designed for installation into compatible fuse holders within electrical panels, control circuits, or other equipment requiring circuit protection. Follow these general guidelines for installation:

  1. ניתוק חשמל: Before beginning any work, ensure that all power to the circuit where the fuse will be installed is completely disconnected and locked out according to safety procedures. Verify with a voltagבודק e.
  2. זיהוי בעל הפיוז: Locate the appropriate fuse holder designed for CC-type cartridge fuses. Ensure the holder is clean and free from debris.
  3. הכנס נתיך: Carefully insert the LP-CC-20 fuse into the fuse holder. Ensure it is seated firmly and correctly within the clips or terminals of the holder. Do not force the fuse.
  4. אמת חיבור: Double-check that the fuse is securely in place and that there are no loose connections.
  5. החזר כוח: לאחר השלמת ההתקנה ואימותה, יש להחזיר את החשמל למעגל.

Note: Always refer to the equipment manufacturer's instructions for specific fuse replacement or installation procedures.

5. עקרונות תפעול

The Bussmann LP-CC-20 fuse operates as a passive safety device. When the current flowing through the circuit exceeds the fuse's 20 Amp rating for a sustained period (time-delay characteristic) or reaches a very high level instantaneously (short-circuit), the internal element of the fuse melts, opening the circuit and preventing damage to equipment or wiring.

  • עיכוב זמן: This feature allows the fuse to withstand temporary overcurrents, common during motor startup or transformer energization, without blowing. This prevents unnecessary interruptions.
  • Current-Limiting: In the event of a severe short circuit, the fuse acts very quickly to limit the peak current and the total energy let-through, thereby reducing the potential for damage to downstream components.

A properly functioning fuse will remain intact under normal operating conditions. It is designed to sacrifice itself to protect the circuit.

6. תחזוקה

Fuses are generally maintenance-free devices. However, periodic inspection of fuse holders and connections is recommended to ensure optimal performance and safety.

  • בדיקה חזותית: Periodically inspect the fuse and its holder for any signs of physical damage, discoloration, or corrosion.
  • שלמות החיבור: Ensure that the fuse holder connections are tight and secure. Loose connections can lead to overheating and premature fuse failure.
  • תַחֲלִיף: If a fuse has blown, it must be replaced. A blown fuse indicates an electrical fault that needs to be investigated and resolved before installing a new fuse.

7. פתרון תקלות

If a circuit protected by an LP-CC-20 fuse loses power, the fuse may have blown. Follow these steps to troubleshoot:

  1. נתק חשמל: Absolutely ensure all power to the affected circuit is disconnected and verified off.
  2. בדוק את הפיוז: Carefully remove the fuse from its holder. Visually inspect the fuse element. A blown fuse will typically show a broken or discolored element. For non-indicating fuses, a multimeter can be used to check for continuity across the fuse. A good fuse will show continuity (near zero resistance), while a blown fuse will show an open circuit (infinite resistance).
  3. זיהוי סיבה: A blown fuse indicates an overcurrent condition. Before replacing the fuse, investigate the cause of the overcurrent. Common causes include:
    • קצר חשמלי בחיווט או בציוד.
    • מעגל עמוס יתר (יותר מדי מכשירים צורכים חשמל).
    • ציוד פגום המחובר למעגל.
    • Motor startup current exceeding normal limits.
  4. Correct Fault: Rectify the underlying electrical fault. Replacing a blown fuse without addressing the cause will likely result in the new fuse blowing immediately.
  5. החלף פיוז: Only after the fault has been corrected, replace the blown fuse with a new Bussmann LP-CC-20 fuse of the identical rating.
  6. החזר כוח: Restore power to the circuit and monitor for proper operation.

If the fuse continues to blow after replacement and fault correction, consult a qualified electrician.

8. אחריות ותמיכה

For warranty information and technical support regarding Bussmann products, please refer to the official Bussmann website or contact their customer service directly. Specific warranty terms may vary based on region and purchase location.

יַצרָן: בוסמן

דֶגֶם: LP-CC-20

UPC: 653829011452

לסיוע נוסף, אנא בקר Eaton's Bussmann Series webאֲתַר.

מסמכים קשורים - LP-CC-20

מִרֹאשׁview מדריך התקנה והרכבה של מתג ניתוק שאינו ניתן לפתיל של Bussmann UL 98
הוראות התקנה והרכבה מקיפות עבור מתגי ניתוק שאינם ניתנים לחיבור UL 98 של Bussmann 100A ו-200A. כוללות אזהרות בטיחות, מידות, תאימות אביזרים ומפרטים טכניים.
מִרֹאשׁview נתיכי להב Bussmann ATC: נתונים טכניים, מפרטים ויישומים
גיליון נתונים טכני מקיף עבור נתיכי להב מסדרת Bussmann ATC. מכסה תיאור מוצר, מאפיינים, דירוגים, מידע על סוכנות, חומרים, מפרטים סביבתיים, מאפיינים חשמליים, מידות ועקומות זמן-זרם עבור תעשיית הרכב ומתח נמוך.tagמעגלי בקרה אלקטרוניים.
מִרֹאשׁview חיבורי נתיכים לאגירת סוללות מסדרת NH של Bussmann - Eaton
גיליון נתונים טכני עבור חיבורי נתיכים לאגירת סוללות מסדרת Bussmann NH של Eaton, המיועדים להגנה ובידוד של מחברי ומנתקי מערכי סוללות. המאפיינים כוללים עיצוב קומפקטי, אובדן הספק נמוך, הסמכות גלובליות, מחוון כפול ואפשרויות חיבור שונות.
מִרֹאשׁview Bussmann Low-Peak LPJ Class J Fuses: Dual Element, Time-Delay, 600Vac/300Vdc
Technical data for Bussmann Low-Peak LPJ Class J fuses, featuring dual-element, time-delay operation, 600Vac/300Vdc ratings, and 1-60A current range. Includes specifications, features, dimensions, and application information.
מִרֹאשׁview Bussmann Series Low-Peak Upgrade Program for Enhanced Fuse Inventory Management
Discover the Bussmann Series Low-Peak Upgrade Program to improve electrical system safety, reliability, and simplify inventory. Learn about the benefits, the 3-step process, and the range of Low-Peak fuses available.
מִרֹאשׁview Bussmann FWH Series Fast-Acting Cartridge Fuses (6x32mm) - Technical Data
Technical datasheet for Bussmann FWH series fast-acting cartridge fuses, 6x32mm. Features include high interrupting rating, low power dissipation, and compliance with RoHS and CE standards. Specifications for voltage, current, opening times, and catalog numbers are provided.