Johnson Controls V-9012-1

מדריך הוראות לממסר שסתום סולנואיד V-9012-1 של Johnson Controls

Model: V-9012-1

1. הקדמה

This manual provides detailed instructions for the installation, operation, and maintenance of the Johnson Controls V-9012-1 E/P Solenoid Relay. This device is designed to convert an electrical signal into a pneumatic output, controlling air pressure based on a 12 VDC input. Please read this manual thoroughly before attempting any installation or operation to ensure safe and efficient use of the product.

2. מידע בטיחות

Adherence to safety precautions is crucial for preventing injury and damage to the equipment. Always follow local codes and regulations.

  • טכנאי מוסמך: Installation and servicing must be performed by qualified and experienced personnel only.
  • בטיחות חשמל: Disconnect all power to the device and associated equipment before performing any wiring or maintenance. Ensure proper grounding.
  • Pneumatic Safety: Depressurize all pneumatic lines before making or breaking connections. Wear appropriate personal protective equipment.
  • תנאים סביבתיים: Do not expose the device to conditions outside its specified operating range (temperature, humidity, pressure).

3. המוצר נגמרview

The Johnson Controls V-9012-1 is an Electro-Pneumatic (E/P) Solenoid Relay that converts a 12 VDC electrical input into a pneumatic control signal. It is commonly used in industrial applications to manage air pressure for actuators or other pneumatic devices.

3.1. תכונות עיקריות

  • 12 VDC Input for electrical control.
  • Solenoid Valve functionality for precise pneumatic regulation.
  • Relay operation for switching pneumatic states.
  • Maximum input current of 50 mA.

3.2. Components and Labeling

Refer to the image below for a visual representation of the V-9012-1 Solenoid Valve Relay and its key labeled components.

Johnson Controls V-9012-1 E/P Solenoid Relay with labels

Figure 1: Johnson Controls V-9012-1 E/P Solenoid Relay

The image displays the Johnson Controls V-9012-1 E/P Solenoid Relay. Key labels visible on the device include:

  • V-9012-1 E/P SOLENOID RELAY: Identifies the model and type of device.
  • PAT 4,770,200 and PAT 4,804,009: Patent numbers associated with the product.
  • BO TERM. 1 (RED): Indicates the first electrical terminal, typically for the positive 12 VDC input.
  • 12 V.D.C. INPUT (50 mA. MAX.): Specifies the required input voltage וזרם מקסימלי.
  • BO TERM. 2 (BLK) RESISTOR: Indicates the second electrical terminal, typically for the negative connection, and notes the presence of a resistor.
  • לְסַפֵּק: The inlet port for the pneumatic supply pressure.
  • ACTUATOR: The outlet port for the controlled pneumatic pressure to the actuator.
  • +12 V.D.C. PRESS.: Indicates that a +12 VDC input results in a 'PRESS' (pressure) state.
  • 0 V.D.C. HOLD: Indicates that 0 VDC input results in a 'HOLD' state.
  • -12 V.D.C. EXHAUST: Indicates that a -12 VDC input results in an 'EXHAUST' state.

4. התקנה והתקנה

Proper installation is critical for the correct functioning of the V-9012-1 Solenoid Relay.

4.1. בדיקות טרום התקנה

  • Verify that the power supply matches the device's requirements (12 VDC).
  • Inspect the device for any visible damage from shipping.
  • ודאו שכל הכלים והאביזרים הדרושים זמינים.

4.2. הַרכָּבָה

Mount the solenoid relay securely in a location that is free from excessive vibration, moisture, and extreme temperatures. Ensure adequate space for wiring and pneumatic connections.

4.3. הוראות חיווט

בצע את השלבים הבאים עבור חיבורי חשמל:

  1. Ensure the power source is completely disconnected.
  2. Connect the positive (+) 12 VDC power supply wire to BO TERM. 1 (RED).
  3. Connect the negative (-) 12 VDC power supply wire to BO TERM. 2 (BLK). Note that this terminal includes a resistor.
  4. ודא שכל החיבורים מאובטחים ומבודדים כהלכה.

4.4. חיבורים פנאומטיים

Follow these steps for pneumatic connections:

  1. Connect the main pneumatic supply line to the port labeled לְסַפֵּק. Ensure the supply pressure is within the device's specified operating range.
  2. Connect the line leading to the pneumatic actuator or controlled device to the port labeled מַפעִיל.
  3. Check all pneumatic connections for leaks after pressurizing the system.

5. תפעול

The V-9012-1 Solenoid Relay operates based on the applied electrical input voltage, controlling the pneumatic output to the actuator.

  • +12 VDC Input: When a positive 12 VDC is applied to the input terminals, the relay will enter a 'PRESS' state, allowing supply pressure to flow to the actuator.
  • 0 VDC Input: When 0 VDC (no voltage) is applied, the relay will enter a 'HOLD' state, maintaining the current pneumatic output.
  • -12 VDC Input: When a negative 12 VDC is applied, the relay will enter an 'EXHAUST' state, releasing pressure from the actuator.

Ensure that the control system provides the correct voltage signals for the desired pneumatic response.

6. תחזוקה

The Johnson Controls V-9012-1 Solenoid Relay is designed for reliable operation with minimal maintenance. However, periodic checks can help ensure longevity and optimal performance.

  • בדיקה שגרתית: Periodically inspect the device for any signs of wear, corrosion, or damage to the housing, wiring, and pneumatic connections.
  • ניקוי: Keep the exterior of the device clean and free from dust and debris. Do not use harsh chemicals or abrasive cleaners.
  • שלמות החיבור: Verify that all electrical and pneumatic connections remain tight and secure.
  • שירות מקצועי: For internal issues or complex repairs, contact a qualified service technician or Johnson Controls support. Do not attempt to disassemble the unit.

7. פתרון תקלות

This section provides solutions to common issues that may arise during the operation of the V-9012-1 Solenoid Relay.

בְּעָיָהסיבה אפשריתפִּתָרוֹן
Device does not respond to electrical input.אין חשמל, עוצמת קול שגויהtage, loose wiring, internal fault.Check 12 VDC power supply. Verify wiring connections to Terminals 1 and 2. Ensure correct polarity. If problem persists, contact support.
Pneumatic output is incorrect or inconsistent.Insufficient supply pressure, clogged lines, leaks in pneumatic connections, internal valve issue.Check pneumatic supply pressure. Inspect lines for obstructions or leaks. Ensure correct electrical input for desired pneumatic state.
המכשיר מתחמם יתר על המידה.Excessive current, improper ventilation, continuous operation beyond duty cycle.Verify input current does not exceed 50 mA. Ensure adequate airflow around the device. Review application for duty cycle requirements.

8. מפרטים

Technical specifications for the Johnson Controls V-9012-1 E/P Solenoid Relay:

פָּרָמֶטֶרעֵרֶך
מספר דגםV-9012-1
פוּנקצִיָהE/P Solenoid Relay
קלט כרךtage12 VDC
זרם קלט מקסימלי50 mA
Pneumatic StatesPress (+12 VDC), Hold (0 VDC), Exhaust (-12 VDC)
יַצרָןג'ונסון בקרות
משקל פריט6.4 אונקיות
תאריך ראשון זמין5 ביולי 2012

9. אחריות ותמיכה

For information regarding product warranty, technical support, or service, please contact Johnson Controls directly through their official website or customer service channels. Keep your purchase receipt and product model number readily available when seeking support.

מסמכים קשורים - V-9012-1

מִרֹאשׁview שסתומי טריז כלוב ברונזה של Johnson Controls: מדריך מוצר 3/4 עד 2 אינץ'
מדריך טכני מקיף עבור שסתומי Bronze Cage Trim של Johnson Controls (3/4 עד 2 אינץ'), המפרט מאפיינים, אפשרויות מפעיל פנאומטי וחשמלי, מפרטים, הפעלה, התקנה וחלקי תיקון עבור יישומי HVAC.
מִרֹאשׁview מתמרים אלקטרו-פנאומטיים מסדרת EP-8000 של Johnson Controls: מפרט טכני, התקנה ותפעול
עלון טכני מפורט עבור מתמרים אלקטרו-פנאומטיים מסדרת EP-8000 של Johnson Controls. מכסה מוצר מעלview, תפעול, מידות, התקנה, חיווט, כיול ומפרטים טכניים עבור יישומי בקרה תעשייתיים.
מִרֹאשׁview מדריך התקנה של שסתומי בקרה מסדרת VG7000 מסדרת ברונזה
הוראות התקנה מקיפות ומפרטים טכניים עבור שסתומי בקרה מסדרת הברונזה VG7000 של Johnson Controls, המיועדים לוויסות מים וקיטור במערכות HVAC. כולל מידות, חומרים ופרמטרי הפעלה של השסתום.
מִרֹאשׁview קטלוג חלקי תיקון שסתומים של ג'ונסון קונטרולס
קטלוג מקיף המפרט חלקי חילוף, כולל דיאפרגמות, ערכות קפיצים, ערכות אריזה, ערכות שיפוץ ורכיבים אחרים עבור מגוון רחב של שסתומים פנאומטיים וחשמליים של Johnson Controls.
מִרֹאשׁview Johnson Controls CSD Series Split Core Current Device Installation Guide
Installation and technical guide for Johnson Controls CSD Series split core current devices (CSD-CF0J1-1, CSD-CA1G1-1) with relay. Covers applications, wiring, calibration, troubleshooting, and specifications for industrial current monitoring.
מִרֹאשׁview מדריך התקנה של שסתום בקרה גלובלי קומפקטי (צירי) VP1000
מדריך התקנה עבור שסתום בקרה VP1000 Compact Globe (Axial) של Johnson Controls, המכסה גדלים של 1/2 אינץ' עד 1 1/4 אינץ' (DN15-DN32). מספק מפרטים טכניים, הוראות הרכבה ומידע על תחזוקה.